CE1R/M/** | Switchable Maintained | ||
---|---|---|---|
CE1R/DA/** | DALI-2 Self-Test Maintained via Mains Switch | ||
CE1R/LMEM/** | LiteMesh Ready Wireless Maintained |
** – Denotes the arrow direction required – e.g. AD for Arrow Down.
The product is supplied in white as a default. If black is required, please use a suffix of /BLK at the end of the code
CE1R/M CE1R/DACE1R/LMEM | |
Mains Supply | 230-240V AC 50/60 Hz |
Power Rating – Charged * | 0.2W 8mA λ = 0.11 |
Power Rating Basic – Charging * | 5.7W 31mA λ = 0.75 |
Power Rating DALI – Charging * | 1.7W 14mA λ = 0.5 |
Duration | 3-Hours |
Recharge Period | 24-Hour – Energy saving electronic charger |
Battery Size & Type | 3.2V 3.8Ah LiFePO4 Cells |
Charge Current | 225mA Nominal |
Ingress Protection | IP40 |
* Following its initial charge, the emergency control gear will spend 90% of its operational life in standby mode.