Code | Description | ||
---|---|---|---|
S/CBH/LED/43/FL/** | 115° 237lm Emergency LED to run from a 50V, 110V or a 240V AC or DC central battery system | ||
S/CBH/LED/43/OA/** | 135° 268lm Emergency LED to run from a 50V, 110V or 240V AC or DC central battery system | ||
S/CBH/LED/43/CO/** | 155° x 115° 266lm Emergency LED to run from a 50V, 110V or 240V AC or DC central battery system |
To determine the power drawn from the central battery system in each scenario, please use the below chart in your calculations:
Supply Voltage |
Output Current (mA) |
Output load |
Supply Current (mA rms) |
Supply Power (W) |
Supply power factor |
Supply VA |
240V AC |
700 |
1 x LED |
36 |
3.60 |
0.41 |
8.8 |
240V DC |
14 |
3.36 |
– |
– |
||
110V AC |
54 |
3.50 |
0.58 |
6.1 |
||
110V DC |
30 |
3.30 |
– |
– |
||
50V AC |
135 |
4.40 |
0.65 |
6.9 |
||
50V DC |
78 |
3.90 |
– |
– |